TU Yaodong, JIANG Yu, GE Tianshu, et al. Analysis on impact factors of energy consumption of novel solid adsorptive dehumidification air-condition system[J]. CIESC Journal, 2014, (z2): 222-227.
TU Yaodong, JIANG Yu, GE Tianshu, et al. Analysis on impact factors of energy consumption of novel solid adsorptive dehumidification air-condition system[J]. CIESC Journal, 2014, (z2): 222-227.DOI: 10.3969/j.issn.0438-1157.2014.z2.033.
The method for determining the best air state point is investigated for a given cooling load and the fresh air volume. Then the relationship between the heat of adsorption of water vapor and the overall energy consumption of solid desiccant air conditioning system is discussed
finally the energy consumption of the novel air conditioning system is compared with conventional condensation dehumidifier. The results showed that the energy consumption of solid desiccant air conditioner is closely related with the heat of adsorption
a reasonable choice hygroscopic agent
not only the energy consumption of the air conditioner condensation dehumidifier is less
especially when a large dehumidification load is treated
the energy saving effect is most obvious. Besides
the supply air temperature difference is smaller
which is helpful for a better comfort indoor air-conditioning environment.