WANG Dong, TAO Leren, TAO Leren. Effect of humidifying amount on defrosting of air cooler in low-temperature cold storage[J]. CIESC Journal, 2014, (z2): 58-63.
WANG Dong, TAO Leren, TAO Leren. Effect of humidifying amount on defrosting of air cooler in low-temperature cold storage[J]. CIESC Journal, 2014, (z2): 58-63.DOI: 10.3969/j.issn.0438-1157.2014.z2.009.
Experimental study of electricity defrosting and hot gas defrosting was done based on a low-temperature cold storage existing. The design of partition device was introduced. The effect of humidifying amount on defrosting time
defrosting load
temperature field around the air-cooler when defrosting were discussed at two kinds of situation with partition device or no. The results show that
with the increasing amount of humidification
defrosting energy consumed also increases accordingly
more than 18% when the humidifying capacity is 1000 g. Electricity defrosting was bigger to the damage degree of cold storage temperature field. The cold storage temperature is increased by 5℃ to 10℃. After the partition device was set up
there was a notable energy conservation effect
the temperature field of cold storage was less destroyed. The maximum change of cold storage temperature is decreased by 5℃ with electricity defrosting. The influence of the partition device to hot gas defrosting was relatively smaller.