ZHANG Penglei, WANG Baolong, HAN Linjun, et al. Comparison of evaporating heat transfer models in two-phase thermosyphon loop[J]. CIESC Journal, 2013, (8): 2752-2759.
ZHANG Penglei, WANG Baolong, HAN Linjun, et al. Comparison of evaporating heat transfer models in two-phase thermosyphon loop[J]. CIESC Journal, 2013, (8): 2752-2759.DOI: 10.3969/j.issn.0438-1157.2013.08.007.
说明核态沸腾在热虹吸管传热中占主导地位; Gungor and Winterton、Liu and Winterton等常用的流动沸腾模型模拟精度差别不大
误差尚可接受;Imura池沸腾模型不适用于热虹吸管传热模拟。
Abstract
Two-phase thermosyphon loop heat exchangers are widely used in different industrial fields.The heat transfer simulation is important for design of thermosyphon.However
due to the complexity of boiling heat transfer and two-phase flow
empirical heat transfer models based on experimental data limit the scope of application
with some difficulties in model choice.In this paper
a mathematical distributed parameter model of two-phase thermosyphon loop is established; the datasets consist of 424 two-phase thermosyphon loop experimental data for 4 working fluids from 5 papers.These datasets are used to evaluate 7 widely used transfer models for evaporation.The results show that Kandlikar's flow boiling model and Rahmatollah's model are the best in calculation accuracy; Cooper's pool boiling model gives relatively good agreement with experimental data
indicating that nucleate boiling is the dominant mechanism; flow boiling models of Gungor and Winterton
Liu and Winterton show similar calculation accuracy and the error is acceptable; but Imura's pool boiling model is not suitable for the thermosyphon heat transfer simulation.