Introduced the design process of the semi-central evaporative cooling air conditioning system in an office building of Xinjiang
combined with the office building structure adopted tandem air -water system.Test results show that the outdoor dry bulb temperature is 35.0℃
and the tertiary evaporative cooling air unit can make the supply air temperature to 13.5℃.The water temperature of indirect-direct evaporative cooling composite chiller is 16.5℃
the indoor maintain in the air conditioning specification requirements of the comfort zone.The paper analyzes the semi-central evaporative cooling air conditioning system’s advantages and disadvantages
and provides some suggestions for evaporative cooling air conditioning system design.