LUO Rong, HUANG Xiang, SHEN Boqing, et al. Performance test and analysis of rotary type two-stage evaporative cooling air conditioning unit[J]. CIESC Journal, 2012, (S2): 146-150.
LUO Rong, HUANG Xiang, SHEN Boqing, et al. Performance test and analysis of rotary type two-stage evaporative cooling air conditioning unit[J]. CIESC Journal, 2012, (S2): 146-150.DOI: 10.3969/j.issn.0438-1157.2012.z2.027.
In order to study the operation of rotary two-stage evaporative cooling air conditioning unit in areas of high humidity
a 3000 m3·h-1 air volume rotary heat recovery-type indirect-direct evaporative cooling air conditioning unit was tested.When opened primary air side rotary indirect evaporative cooling section and filler segment
the pump of secondary air side filler segment was shut down
the supply air temperature of the unit was 23℃
which was lower than the outdoor air dew-point temperature of 24.5℃
the total average temperature drop of the unit was 7.1℃
the average temperature drop of the rotary indirect segment was 6.9℃
the average cooling efficiency of 76.9%
filler segment almost did not play a role in cooling
the dominant cooling rotary indirect segment.The contrast in a dry
moderate humidity areas
the average outdoor dry bulb temperature of 32.1℃
which played a major role in cooling air side filler segment
lower the average temperature up to 5.5℃.This showed whether the indirect
direct
or indirect-direct evaporative cooling could applied where refrigeration refrigeration cooling was expensive.