江燕涛1. Influence of outlet water temperature on heating performance of modular air-cooled chilled (hot)water units with electronic expansion valve[J]. CIESC Journal, 2012, (S1): 154-158.
江燕涛1. Influence of outlet water temperature on heating performance of modular air-cooled chilled (hot)water units with electronic expansion valve[J]. CIESC Journal, 2012, (S1): 154-158.DOI: 10.3969/j.issn.0438-1157.2012.z1.027.
In order to study the impact of the change of outlet water temperature on the heating performance of air-cooled heat pump chiller which adopts electronic expansion value and modularity energy adjustment system,the experiment is carried out on 5 this kind of unit with 60kW refrigerating output in the variable working conditions of outlet water temperature in the range of 39—50℃,ambient temperature in the range of -10~13℃ and relative humidity 90%.The heating capacity of the unit between 34.6—78.8kW,consumed power between 16.2—22.2kW,heating COPh between 1.77—4.20.The effects of outlet-water temperature of condenser on heating capacity,input power and COPh were examined,which provides the basis for energy saving operation and optimization design.