In order to study the effect of outlet-water temperature on the refrigeration performance of modular air-cooled chilled (hot)water with electronic expansion value and modularity energy adjustment system,experiments were carried out with 5 units with 60 kW refrigerating output under different working conditions:outlet water temperature of evaporator chilled water in the range of 5—12℃,ambient dry-bulb temperature in the range of 25—42℃,and relative humidity 40%.The cooling capacity of the unit is 54—71 kW,power consumption is 17.2—22.2 kW,and refrigeration COP is 2.55—3.84.The effect of outlet-water temperature of chilled water on refrigeration capacity,input power and COP were examined,which provides the basis for energy saving operation and optimization design.