CO2 air-source heat pump can operate stably in cold area
which is expected to be popularized and applied in the field of space heating. To evaluate the performance of CO2 air-source heat pump heating objectively and reasonably
the supercritical CO2 air-source heat pump heating system in cold region was built. According to outdoor ambient temperature and heating load
the heating period is divided into five different stages
and the heating operation parameters of CO2 air-source heat pump are adjusted in different stages. The results show that the CO2 air-source heat pump can meet the heating demand in cold area
and the average performance coefficient of the heating system in the heating periods can reach 2.236
at the same time the heating room has good comfort. Taking coal-fired boiler and gas-fired boiler as reference
the energy utilization efficiency and CO2 emission amount of three kinds of heat source heating are compared and analyzed by using equivalent electricity method. The results show that the energy utilization efficiency of CO2 air source heat pump heating is higher than that of gas boiler heating and is slightly lower than that of coal-fired boiler heating after considering the energy grade. The CO2 emission amount of CO2 air-source heat pump heating is higher than that of gas-fired boiler heating