LI Weihao, ZHANG Xiaosong. Experimental research on a new type of frost-free air source heat pump system[J]. CIESC Journal, 2018, (9): 3975-3982.DOI: 10.11949/j.issn.0438-1157.20180150.
This paper reports an experimental research of a new type of air source heat pump system in summer. This system can operate efficiently in winter
and improve the performance in summer operation. Through constructing the experimental platform for heat pump system
the effects of outdoor air dry bulb temperature
relative humidity
chilled water flow rate
cooling water flow rate and outdoor air flow rate in summer conditions on system performance can be acquired. It is concluded that the COP of air source heat pump air conditioning system increases with the decrease of outdoor air humidity
the increase of cooling water flow rate and the increase of chilled water flow rate. The effects of outdoor air flow rate on system performance can be ignored. At the condition of outdoor air dry bulb temperature 35℃ and relative humidity 45%
the COP of system can reach 3.23
more than the COP of compressor rated
which fully demonstrated that the system can run stably and efficiently in summer.