XU Junfang, ZHAO Yaohua, QUAN Zhenhua, et al. Defrosting characteristics and energy consumption of new air-water dual source composite heat pump system[J]. CIESC Journal, 2018, (6): 2646-2654.
XU Junfang, ZHAO Yaohua, QUAN Zhenhua, et al. Defrosting characteristics and energy consumption of new air-water dual source composite heat pump system[J]. CIESC Journal, 2018, (6): 2646-2654.DOI: 10.11949/j.issn.0438-1157.20171277.
Based on the operation testing of new air-water double source composite heat pump system (AWDSHPS-N)
three defrosting modes were investigated under the same ambient condition
which included the condenser outlet refrigerant recooling defrosting(D-I)
the low temperature-hot water defrosting(D-Ⅱ)
the condenser outlet refrigerant recooling and low temperature-hot water defrosting at same time (D-Ⅲ). Total coefficient of performance (COP) of AWDSHPS-N was used to evaluate the influence of the three modes. The influence on the total COP
defrosting operating characteristics and energy consumption of D-I
D-Ⅱ and D-Ⅲ were discussed and compared with those in the reverse-cycle defrosting mode
under the same ambient condition. The results of test conditions indicated that for D-I and D-Ⅱ
the total COP can be decreased by 0.42% and 3.93%
respectively
compared with the COP of frosting period. The heating power and COP during D-Ⅱ defrosting were 27.4% and 17.8% higher than those of frosting operation
respectively. The total COP of AWDSHPS-N choosing D-I
D-Ⅱ and D-Ⅲ were 26.06%
29.79% and 17.02% higher than that of verse-cycle defrosting
and the defrosting energy consumption of D-I
D-Ⅱ and D-Ⅲ were only 3.11%
34.78% and 28.26% of the reverse-cycle defrosting energy consumption.