Pointing at the unfavorable conditions and improving the reliability of the drying system
a coupled application scheme of low-temperature heat pump(LTHP) and dry heat pump(DHP) is proposed
according to the principle of two stage compression refrigeration cycle. By using the exergy analysis model
the exergy loss of the heat
the mass diffusion of the drying medium and the dehumidification process were analyzed respectively to the drying system. With the LTHP at 20
22
24
26
28
30℃ and closed
the experiment tests and calculates the exhaust temperature and energy consumption of the compressor of DHP
coefficient of performance and the thermodynamic perfect degrees. The drying time and energy consumption of the system were measured when the water content of wood was decreased by 1%
at different heating temperatures. The results show that:compared with shutting down the LTHP
the exhaust temperature of the drying heat pump is reduced by 16℃ at most
and all the performance coefficient of the heat pump is improved. By the increase of the temperature of the machine hall
the irreversibility of the system cycle increases
and the thermodynamic perfect degrees decreases gradually. After opening the LTHP
the maximum amount of heating load and the drying time of the DHP increases by 44% and decreases by 46%