XU Shengzhi, WANG Liwei, WANG Ruzhu. Thermodynamic analysis of mass and heat recovery adsorption refrigeration cycles and scheme selection[J]. CIESC Journal, 2016, (6): 2202-2210.
XU Shengzhi, WANG Liwei, WANG Ruzhu. Thermodynamic analysis of mass and heat recovery adsorption refrigeration cycles and scheme selection[J]. CIESC Journal, 2016, (6): 2202-2210.DOI: 10.11949/j.issn.0438-1157.20151803.
Adsorption refrigeration is an energy-saving and environmental-friendly refrigerating method
which can utilize low-grade thermal energy. Under air-conditioning working conditions
silica gel-water mass and heat recovery systems are most often used. In order to understand which kind of cycle can improve the performance of the system under specific working conditions
the evaluating indicators of the first and the second laws of thermodynamics were adopted to analyze the COP
the exergetic efficiency and the cycle entropy production of the basic cycle
mass recovery cycle and mass and heat recovery cycle. The analysis showed that only when the heating source temperature was relatively low
the COP of mass recovery cycle was remarkably higher than that of basic cycle. The COP of mass and heat recovery cycle was significantly higher than that of mass recovery cycle only when the heating source temperature was relatively high. Consequently
the mass recovery cycle had its recommended highest heating source temperature and optimum heating source temperature
while the mass and heat recovery cycle had its recommended lowest heating source temperature and optimum heating source temperature. For example
under the typical air-conditioning working condition in summer of 90℃ heating source temperature
10℃ evaporating temperature and 40℃ condensing temperature
the recommended highest heating source temperature of mass recovery cycle was 93℃
which is higher than the heating source temperature of 90℃. As a result
the mass recovery cycle was more suitable under this working condition and should be chosen rather than the mass and heat recovery cycle. Finally
the analysis of a chiller indicated that the given method and recommended working temperature intervals could provide guidance or advice on the scheme selection and system control for real systems.