Suction line heat exchanger is used for inner heat recovery with which heat is exchanged between condensed refrigerant liquid and evaporated refrigerant gas. In a general refrigeration system
inner heat recovery is helpful to increase cooling output
but it may lower the performance of vapor compressing refrigeration system sometimes also. In adsorption refrigeration cycle
inner heat recovery is beneficial to improve the cycle performance in terms of quantitative thermodynamic analysis. Although inner heat recovery decreases the cooling effect to adsorbent from evaporated gas
this does not offset the tendency of increasing cooling output. Some experimental data also verify that the precooler recovers some heat from the evaporated gas and help the evaporator to provide much more cooling capacity. Therefore
in adsorption refrigeration system
the precooler for inner heat recovery is an effective element to improve its performance
especially in the situation that condensing temperature is far higher than evaporating temperature.