Liquid desiccant air conditioning systems have become popular because of the advantage in removal of latent heat load. Regeneration performance is experimentally studied on a liquid regenerator filled with novel Z-type packing (specific surface area 160 m2·m-3) and corrugated structured packing (specific surface area 450 m2·m-3).The results show that
under the same operating condition in winter
the regeneration rate
the regeneration efficiency and the regeneration thermal efficiency of Z-type packing are about 40%
50% and 70% of the corrugated structured packing respectively. In addition
all the regeneration performance indicators have large space to improve through reducing the space between Z-type units. The Z-type packing in liquid desiccant regenerator is promising compared with the corrugated structured packing.
Performance of regeneration processes of internally heated regenerator and adiabatic regenerator
Performance of solar liquid desiccant regeneration
Experimental investigation and model validation for liquid desiccant dehumidification and regeneration in falling-film plate
Investigation on the dynamics and vaporization characteristics of droplet impact on the heated wall surface
Improvement and numerical validation of quasi-steady-state frosting model based on thermal and mass transfer effect
Related Author
WANG Qin
WU Wei
LIU Songsong
GU Chenjie
CHEN Cong
TANG Zhibiao
QIAN Junfei
ZHANG Youchao
Related Institution
Engineering Laboratory for Energy System Process Conversion and Emission Control Technology of Jiangsu Province, School of Energy and Mechanical Engineering, Nanjing Normal University
College of Energy Power and Mechanical Engineering, North China Electric Power University
Energy Storage and Novel Technology of Electrical Engineering Department, China Electric Power Research Institute Limited Company
School of Mechanical Engineering, Lanzhou Jiaotong University
Key Laboratory of Railway Vehicle Thermal Engineering, Ministry of Education