Mathematical modeling for height of absorption region in spray tower for limestone-gypsum wet flue gas desulfurization
Specific surface area and mass transfer rate in spray tower were studied by considering the forces acting on a droplet. Absorption region was divided into accelerating segment and constant speed segment
and a segmentation calculation model for the height of absorption region was developed
which was verified by the data of four industrial desulfurization systems. The effects of operating parameters on the height of absorption region were investigated. The results show that height of absorption region decreases with the decrease of spray density and pH value of absorbent
and increases with the decrease of droplet diameter
superficial gas velocity and inlet SO2 concentration. The desulfurization efficiency increases with the height of absorption region. When the desulfurization efficiency reaches above 90%
the height of absorption region only has a slightly influence on the efficiency.