Experimental study of different charging ratios on operational characteristic of new-type loop heat pipe
which can be applied for the high heat flux components such as CPU
data center
etc. During the operation of LHP
the pressure head due to evaporation cannot be ignored. The LHP is different from the LHP with capillary force
the wick is separated from the heating surface and then a steam chamber is formed
in which the pressure head due to evaporation can be effectively used. The influence of different charging ratios (15%-85%) on the operational characteristic of such a LHP is studied through experiment. The result showed such a LHP can operate in a wide charging ratio (20%-75%) and there existed an optimal charging ratio
which is 35%. Under the optimal charging ratio
the temperature of evaporator bottom was 65.1℃. Through the experimental research of different charging ratios
it can provide reference for the optimization of loop heat pipe design for different heat load heat dissipation and can guide the subsequent experimental research.