NING Jinghong, LIU Shengchun. Performance analysis on direct contact condensation refrigeration cycle of high temperature gas with super-cooled liquid[J]. CIESC Journal, 2018, (4): 1437-1444.
DOI:
NING Jinghong, LIU Shengchun. Performance analysis on direct contact condensation refrigeration cycle of high temperature gas with super-cooled liquid[J]. CIESC Journal, 2018, (4): 1437-1444.DOI: 10.11949/j.issn.0438-1157.20170122.
Performance analysis on direct contact condensation refrigeration cycle of high temperature gas with super-cooled liquid
The direct contact condensation refrigeration cycle of high temperature gas discharged by compressor with super-cooled liquid is designed. Combined with the thermodynamic properties of natural refrigerant ammonia
the thermal performances of direct contact condensation refrigeration cycle are analyzed and compared with that of convention two stage compression refrigeration cycle and one stage compression refrigeration cycle. The following conclusions are obtained. With the increasing of saturated liquid temperature of main cycle
the coefficient of performance (COP) of direct contact condensation refrigeration cycle first increases
then decreases and has the maximum
the condenser heat load first decreases
then increases and has the minimum. The refrigerant mass flow rate in evaporator is gradually increasing. At the same evaporating and condensation temperature
when the super cooling degree of supercooled liquid is 20℃
compared with that of conventional two stage compression refrigeration cycle
the COP of direct contact condensation refrigeration cycle increases 4.92%
the condenser heat load reduces 6.65%
and the refrigerant mass flow rate in evaporator reduces 7.2%-7.9%. As well as when the super cooling degree of supercooled liquid is 5℃
compared with that of conventional one stage compression refrigeration cycle
the COP of direct contact condensation refrigeration cycle increases 6.52%
the condenser heat load reduces 3.32%
and refrigerant mass flow rate in the evaporator reduces 8.58%-8.91%. The results show that the ammonia direct contact condensation refrigeration cycle has obvious advantages over the conventional refrigeration cycle.