System performance and defrosting test of new air-water double source composite heat pump system
In order to improve many disadvantages that the heat pump system has when it uses the reverse-cycle defrosting method in the low temperature environment
a new air-water double source composite heat pump system (AWDSHPS-N) was presented. This system has a new preheating and defrosting function. AWDSHPS-N has defrosted for 5 min and has 5 different defrosting ways
such as the condenser outlet refrigerant recooling defrosting
the low temperature-hot water defrosting
and so on. It can be put into different modes by changing some relevant valves or starting and stopping the pump of the low temperature water. In this way
the heat output power of AWDSHPS-N may be reduced dramatically
but the system can produce heating continuously. A test-bed including constant temperature and humidity environment storehouse and a low temperature water tank were set up to get operating data for coefficient of performance (COP) of AWDSHPS-N. The environment storehouse imitates the change in outdoor environment by keeping the temperature and the humidity at a certain level constantly
and the low temperature water tank with two electric heating bars can be thought as a low temperature heating source of a solar energy system or a waste heat system. By heating the water from 18℃ to 51℃
the COP of AWDSHPS-N was tested and analyzed in air source heating mode (ASHM)
water source heating mode (ASHM)
water source heating mode (WSHM) and air-water double source heating mode (AWSHM)
respectively. By calculating
the COP of AWSHM is 6.1%-20.5% higher than ASHM. When the ambient temperature and the low temperature water are both above 15℃
the COP of AWSHM is the best one
and the COP of WSHM is the last one among these three heating modes.
Structural design and effect verification of casing-type distributor used in air-conditioners
Process design of 10000 t industrial demonstration of hydrogen production from renewable energy electrolytic water - low temperature and low pressure ammonia synthesis
Comparative study on leakage and film-forming characteristics of oil-gas seal with three-typical groove in a wide speed range
Thermodynamic analysis and operation optimization of multi energy complementary energy storage system
Variable working condition adaptability of cone core adjustable ejector
Related Author
YAN Ziteng
ZHAN Feilong
DING Guoliang
YIN Mengfan
WANG Qian
ZHENG Tao
JI Kui
WANG Shaogui
Related Institution
Institute of Refrigeration and Cryogenics, Shanghai Jiao Tong University
State Key Laboratory of Heavy Oil Processing, China University of Petroleum
Ningxia Hening Chemical Co., Ltd.
College of Mechanical Engineering, Zhejiang University of Technology
Science and Technology on Diesel Engine Turbocharging Laboratory, China North Engine Research Institute