An experimental investigation of falling-film generation outside vertical tube with lithium chloride aqueous solution was conducted.For the purpose of the development of a high performance of heat and mass transfer utilizing a lithium chloride aqueous solution as the working pair in solar absorption refrigeration system which use the low grade source
an experimental apparatus is set up to study the process of heat and mass transfer in generator using low temperature source.The experiments show that how the operation conditions such as the flow rate of hot water and the solution
the temperature of the heat source
the concentration of the solution and the system pressure influent the generation process.Some contrast experiments at the same condition with lithium bromide are carried on.The variation trend of the vertical falling film generation with lithium chloride aqueous solution is similar with that with lithium bromide aqueous solution.Although the mass rate of falling film generation with lithium chloride aqueous solution is slightly lower than that using lithium bromide aqueous solution
it has little difference in the effect of heat and mass transfer
and it is good for the performance of the system cycle which using the two working pairs becoming higher at the same condition because of the low operation concentration of lithium chloride aqueous solution.
Identification of gas-liquid two-phase flow patterns in a riser based on recursive characteristics and CNN
Study on performance enhancement and cold retention characteristics of solid packed bed cold energy storage
Calibration method and experimental validation for resolving inverse heat conduction problem with constant temperature on back surface
Development of skeletal combustion reaction kinetics mechanism for ammonia/hydrogen co-combustion process
Experimental study on influence of inner tube movement on charging-discharging performance in horizontal shell-and-tube phase change thermal energy storage exchanger
Related Author
WANG Jiahao
HUANG Yuecheng
ZHANG Yifan
ZHANG Jialue
WEI Desheng
SU Ruoxi
HUANG Kun
LI Nailiang
Related Institution
School of Low-carbon Energy and Power Engineering, China University of Mining and Technology
School of Mechanical and Storage and Transportation Engineering, China University of Petroleum
College of Energy Engineering, Zhejiang University
School of Aeronautics and Astronautics, Zhejiang University
State Key Laboratory of Chemical Engineering and Low-carbon Technology, School of Chemical Engineer and Technology, Tianjin University