HUO Erguang, DAI Yuande, GENG Ping, et al. Feasibility of using R1234ze and R152a mixture as alternative for R22[J]. CIESC Journal, 2015, (12): 4725-4729.
DOI:
HUO Erguang, DAI Yuande, GENG Ping, et al. Feasibility of using R1234ze and R152a mixture as alternative for R22[J]. CIESC Journal, 2015, (12): 4725-4729.DOI: 10.11949/j.issn.0438-1157.20151281.
Feasibility of using R1234ze and R152a mixture as alternative for R22
R410A and R407C are the main alternative refrigerants of R22. Their ODP is zero
but their GWP is relatively high
with a negative impact on the environment. For the selected mixed refrigerant composed of mass fraction of 40% of R1234ze and 60% R152a (represented by NCUR01)
its theoretical analyses according to REFOROP9.0
analyzing its environmental impact index
its temperature glide characteristics
theoretical thermodynamic cycle performance
thermodynamic properties
safety and lubricants
and other factors are carried out and compared with R22
its major alternative refrigerants R410A and R407C. The results show that the mixed refrigerant has very small impact on the environment
presents similar saturation pressure line to that of R22
and has a lower discharge temperature and a higher COP. The discharge temperature of NCUR01 is 18℃ lower than that of R22 and R410A
6℃ lower than that of R407C. COP of NCUR01 is about 5% higher than that of R22
19.6% higher than R410A
and 9.7% higher than R407C. Thus it is an excellent near-azeotropic refrigerant