HE Jiaji, LIU Jinping, PANG Weiqiang, et al. Analysis and experimental investigation on mass charge of mixed refrigerantsin Linde-Hampson coolers[J]. CIESC Journal, 2015, (12): 5002-5011.
DOI:
HE Jiaji, LIU Jinping, PANG Weiqiang, et al. Analysis and experimental investigation on mass charge of mixed refrigerantsin Linde-Hampson coolers[J]. CIESC Journal, 2015, (12): 5002-5011.DOI: 10.11949/j.issn.0438-1157.20150402.
Analysis and experimental investigation on mass charge of mixed refrigerantsin Linde-Hampson coolers
The refrigerant charging quantity has significant effect on the performance of a refrigeration system. For a specific mixed refrigerant (MR) Joule-Thomson cooler
proper MR charging quantity is determined by operation pressure
temperature and concentration of components. It is difficult to determine the optimal MR charging quantity by means of experimental test
so a MR mass charge prediction model is established in this paper. Using the integral method
the Linde-Hampson cooler is divided into four parts to calculate the MR mass distribution and the liquid hold-up. The calculation result shows that
over 60% of the MR is accumulated in the hot steam of the recuperative heat exchanger
the liquid MR occupies more than 80% of the total charging quantity
and the mass of liquid MR will increase as the refrigerating temperature decreases. An experimental investigation is used to verify the accuracy of this model. The result shows that
in the refrigeration temperature of -100-60℃
the deviation between the calculated MR charging quantity and actual one is not more than 20%. The deviation between the calculated proportion of components and the experimental result is also less than 20%.