LUO Huilong, LIN Bianqi, DU Peijian, et al. Investigation of operational performance of high power CO2 heat pump hot water system[J]. CIESC Journal, 2015, (6): 2274-2279. DOI: 10.11949/j.issn.0438-1157.20150049.
DOI:
LUO Huilong, LIN Bianqi, DU Peijian, et al. Investigation of operational performance of high power CO2 heat pump hot water system[J]. CIESC Journal, 2015, (6): 2274-2279. DOI: 10.11949/j.issn.0438-1157.20150049.DOI:
Investigation of operational performance of high power CO2 heat pump hot water system
A high power transcritical CO2 heat pump hot water system was designed and built on the basis of the existing low power water heater. In order to improve system efficiency
two-stage gas cooler
dual capillary tube combination throttle and internal heat exchanger were used in the CO2 heat pump hot water system. The effects of climatic and operational parameters on the steady state thermal performance of the CO2 heat pump hot water system were tested and analyzed in the constant temperature environmental chamber. Test results under typical climate conditions showed that system performance was excellent. The CO2 heat pump hot water system could provide 60—85℃ hot water according to climatic conditions
and its daily COP (coefficient of performance) was about 3.45—4.04 under the climatic conditions of ambient temperature at 4.1 to 27.3℃.