Two Phase Flow and Heat Transfer in VerticalU-Shaped Tubes(Ⅱ) Deterioration of Boiling Heat Transfer in Waste Heat Boilers
|更新时间:2025-12-16
|
Two Phase Flow and Heat Transfer in VerticalU-Shaped Tubes(Ⅱ) Deterioration of Boiling Heat Transfer in Waste Heat Boilers
CIESC JournalIssue 4, (1985)
作者机构:
西安交通大学,西安交通大学,西安交通大学,西安交通大学,西安交通大学
作者简介:
基金信息:
DOI:
CLC:
Online First:25 December 1985,
Published:25 December 1985
稿件说明:
移动端阅览
Chen Tingkuan, Gu Yaping, Luo Yushan, et al. Two Phase Flow and Heat Transfer in VerticalU-Shaped Tubes(Ⅱ) Deterioration of Boiling Heat Transfer in Waste Heat Boilers[J]. CIESC Journal, 1985, (4).
DOI:
Chen Tingkuan, Gu Yaping, Luo Yushan, et al. Two Phase Flow and Heat Transfer in VerticalU-Shaped Tubes(Ⅱ) Deterioration of Boiling Heat Transfer in Waste Heat Boilers[J]. CIESC Journal, 1985, (4).DOI:
Two Phase Flow and Heat Transfer in VerticalU-Shaped Tubes(Ⅱ) Deterioration of Boiling Heat Transfer in Waste Heat Boilers
In order to clarify the cause of failure in waste heat boilers with vertical U-shaped tubes
variation of wall temperature along the bend under thermal conditions was investigated in an electrically heated high pressure water loop experimental installation. The water loop consisted of a 25 mm i. d. stainless steel tube with a 180° bend of radius 700 mm operating under the conditions of P=106×105Pa
G=800-2000 kg/m2·s and q = 80-330kW/m2·In the tests
the circumferential wall temperature profile along the bend was found to increase from the middle of the downward section of the tube to 15°of the upward section
at low mass velocities and low steam qualities
reaching a peak value at (?)=75°. The temperature difference
△t
between the inner side and outer side of the bend was found to vary with mass velocity
steam quality and heat flux
increasing abruptly to a peak value at low steam qualities. Variation of △t was noted to reflect the influence of flow pattern transitions. As may be anticipated
the flow regime belongs to stratified flow for low mass velocities and low steam qualities. In this regime
slow-moving vapor
packets on the inner wall of the bend
and hence low heat transfer rates may be expected to lead to large temperature gradients. For bigher steam qualities
inter-mittent two-phase flow may be expected to reduce the temperature difference. Finally
appearance of liquid film around the tube wall in the annular flow regime may be anticipated to result in considerable suppression of the temperature difference.