Research on model-plant mismatch detection based on subspace approach
摘要
Abstract
As a key factor in model-based control technique
model fidelity has significant influence on control performance.Model-plant mismatch(MPM)is an important step in the procedure of control performance monitoring and system maintenance.A subspace-based MPM approach for control systems was proposed.First
the residual was constructed through subspace transformation.Then the residual was analyzed by using statistical local approach
from which an indicator could be constructed to detect the mismatch.Using orthogonal subspace
it was not needed to estimate system states and residual could be obtained only by using input and output data.Furthermore
based on the state space model
the proposed approach was suitable for MIMO process.The effectiveness of the proposed approach was illustrated by both simulation and industrial applications.