Heat and mass transfer coefficients of liquid desiccant dehumidification/regeneration processes with non-thermal equilibrium(Ⅰ) Model and Le-hD evaluation method
|更新时间:2025-12-10
|
Heat and mass transfer coefficients of liquid desiccant dehumidification/regeneration processes with non-thermal equilibrium(Ⅰ) Model and Le-hD evaluation method
CIESC JournalIssue 9, (2011)
作者机构:
1. 1南昌大学建筑工程学院,江西,南昌,330031
2. 东南大学能源与环境学院,江苏,南京,210096
3. 上海核工程研究设计院,上海,200233
作者简介:
基金信息:
DOI:
CLC:
Online First:05 September 2011,
Published:05 September 2011
稿件说明:
移动端阅览
彭冬根1, 3. Heat and mass transfer coefficients of liquid desiccant dehumidification/regeneration processes with non-thermal equilibrium(Ⅰ) Model and Le-hD evaluation method[J]. CIESC Journal, 2011, (9).
DOI:
彭冬根1, 3. Heat and mass transfer coefficients of liquid desiccant dehumidification/regeneration processes with non-thermal equilibrium(Ⅰ) Model and Le-hD evaluation method[J]. CIESC Journal, 2011, (9).DOI:
Heat and mass transfer coefficients of liquid desiccant dehumidification/regeneration processes with non-thermal equilibrium(Ⅰ) Model and Le-hD evaluation method
The liquid dehumidifiers are the key unit for liquid desiccant cooling system(LDCS)and the internal heat and mass transfer of dehumidifier have important influence on the performance of LDCS.Based on the adiabatic dehumidification model
a new model considering non-thermal equilibrium was put forward to evaluate heat and mass transfer coefficients.By simulation calculation
it is found that the outlet parameters of air and liquid from non-thermal equilibrium model agree well with the experimental values
so that the model is better to evaluate heat and mass transfer coefficients.When the heat capacity rate ratio C*≥1.0
the calculation results for the number of mass transfer units and Lewis factor from non-thermal equilibrium model are much better than those from the adiabatic model
while the two models give almost the same results when C*≤0.05.