An analysis for heat and moisture transfer effect in air-water or -hydroscopic solution (Ⅰ)Reachable handling region
|更新时间:2025-12-10
|
An analysis for heat and moisture transfer effect in air-water or -hydroscopic solution (Ⅰ)Reachable handling region
CIESC JournalIssue 11, (2011)
作者机构:
清华大学建筑技术科学系
作者简介:
基金信息:
DOI:
CLC:0.3969/j.issn.0438-1157.2011.11.004
Online First:05 November 2011,
Published:05 November 2011
稿件说明:
移动端阅览
张涛. An analysis for heat and moisture transfer effect in air-water or -hydroscopic solution (Ⅰ)Reachable handling region[J]. CIESC Journal, 2011, (11).
DOI:
张涛. An analysis for heat and moisture transfer effect in air-water or -hydroscopic solution (Ⅰ)Reachable handling region[J]. CIESC Journal, 2011, (11).DOI:
An analysis for heat and moisture transfer effect in air-water or -hydroscopic solution (Ⅰ)Reachable handling region
A model is established to analyze the heat and moisture transfer process in air-water or - hydroscopic solution system
two independent driving forces each other: enthalpy difference and relative humidity difference can be obtained. A triangle region
consisting of iso-enthalpy line from air inlet
saturation line of moisture air(iso-concentration line of solution)and connecting line of air and water or solution at inlet status
is determined in enthalpy-psychrometric chart based on relationship between the two driving forces. The region is a reachable handling region for heat and moisture transfer process in air-water or-hydroscopic solution system
because the variation of air outlet status is limited in the region whatever change of mass and heat transfer coefficients or flow pattern and rate. Experimental results of dehumidification and regeneration in literatures are analyzed with the help of reachable handling region.