Relationship between water quality parameters and fouling in plate heat exchangers
|更新时间:2025-12-10
|
Relationship between water quality parameters and fouling in plate heat exchangers
CIESC JournalIssue 2, Pages: 344-347(2011)
作者机构:
东北电力大学能源与动力工程学院
作者简介:
基金信息:
DOI:
CLC:
Online First:05 February 2011,
Published:05 February 2011
稿件说明:
移动端阅览
XU Zhiming, GUO Jinsheng, HUANG Xing, et al. Relationship between water quality parameters and fouling in plate heat exchangers[J]. CIESC Journal, 2011, (2): 344-347.
DOI:
XU Zhiming, GUO Jinsheng, HUANG Xing, et al. Relationship between water quality parameters and fouling in plate heat exchangers[J]. CIESC Journal, 2011, (2): 344-347.DOI:
Relationship between water quality parameters and fouling in plate heat exchangers
The relationship between fouling thermal resistance in a plate heat exchanger and water quality parameters such as iron
total bacteria
pH
dissolved oxygen
turbidity and conductivity in the Songhua River water was investigated.Results show that the value of the fouling thermal resistance in the plate heat exchanger is lower than that of Tubular Exchanger Manufacturers Association (TEMA)
and the natural cooling water has no induction period.pH and dissolved oxygen influence the iron corrosion rate and total bacteria
which affects the turbidity and conductivity.All these parameters have considerable effects on the heat transfer performance in the initial period
and then the effects are less.There exists synergetic effects from different fouling causes
and the fouling can be inhibited by reducing the amount of dissolved oxygen and total bacteria.