Airside heat and mass transfer characteristics of split fin-and-tube heat exchangers under dehumidifying conditions
|更新时间:2025-12-10
|
Airside heat and mass transfer characteristics of split fin-and-tube heat exchangers under dehumidifying conditions
CIESC JournalIssue 8, Pages: 1911-1916(2007)
作者机构:
上海交通大学制冷与低温工程研究所
作者简介:
基金信息:
DOI:
CLC:
Online First:05 August 2007,
Published:05 August 2007
稿件说明:
移动端阅览
MA Xiaokui, DING Guoliang, ZHANG Yuanming. Airside heat and mass transfer characteristics of split fin-and-tube heat exchangers under dehumidifying conditions[J]. CIESC Journal, 2007, (8): 1911-1916.
DOI:
MA Xiaokui, DING Guoliang, ZHANG Yuanming. Airside heat and mass transfer characteristics of split fin-and-tube heat exchangers under dehumidifying conditions[J]. CIESC Journal, 2007, (8): 1911-1916.DOI:
Airside heat and mass transfer characteristics of split fin-and-tube heat exchangers under dehumidifying conditions
The airside heat and mass transfer characteristics of seven split fin-and-tube heat exchangers with hydrophilic coating were studied under dehumidifying conditions experimentally. The effects of fin pitch and inlet relative humidity on airside heat and mass transfer performance were investigated. The results indicated that the heat and mass transfer performance decreased with the increase of fin pitch. The heat transfer performance was insensitive to the change of inlet relative humidity
and the mass transfer became weaker with the rise of inlet relative humidity. Correlations were proposed to describe the heat and mass transfer characteristics. The Colburn heat transfer factors Jh correlation could describe 96.6% of experimental data and the Colburn mass transfer factors Jm correlation could describe 81.4% of experimental data with an error of ±15%.Correspondingly
the mean deviations of the proposed heat and mass transfer correlation were 5.3% and 8.5%