FLOW EVAPORATION HEAT TRANSFER AND PRESSURE DROP IN HORIZONTAL MICRO-FIN TUBES
|更新时间:2025-12-10
|
FLOW EVAPORATION HEAT TRANSFER AND PRESSURE DROP IN HORIZONTAL MICRO-FIN TUBES
CIESC JournalIssue 9, Pages: 1215-1219(2003)
作者机构:
清华大学热能工程系,北京,100084
作者简介:
基金信息:
DOI:
CLC:
Online First:25 September 2003,
Published:25 September 2003
稿件说明:
移动端阅览
WU Xiaomin, WANG Xiaoliang, WANG Weicheng. FLOW EVAPORATION HEAT TRANSFER AND PRESSURE DROP IN HORIZONTAL MICRO-FIN TUBES[J]. CIESC Journal, 2003, (9): 1215-1219.
DOI:
WU Xiaomin, WANG Xiaoliang, WANG Weicheng. FLOW EVAPORATION HEAT TRANSFER AND PRESSURE DROP IN HORIZONTAL MICRO-FIN TUBES[J]. CIESC Journal, 2003, (9): 1215-1219.DOI:
FLOW EVAPORATION HEAT TRANSFER AND PRESSURE DROP IN HORIZONTAL MICRO-FIN TUBES
To investigate the effects of micro-fin geometry and operating conditions on flow evaporation performance of micro-fin tubes
tests were conducted on four micro-fin tubes having different micro-fin geometries and one smooth tube having 9.52mm outside diameter (OD). Two of the micro-fin tubes had 9.52mm OD and the remaining two had 7.0mm OD.The refrigerant used was R22. The experiments were carried out for 90—400kg8226;m-28226;s-1 refrigerant mass fluxes at 7℃ evaporation temperature
15%—20% inlet vapor quality
5—6℃ outlet superheat degrees. The variations of evaporation performance of micro-fin tubes with refrigerant mass flux were obtained. The effects of micro-fin geometry and tube diameter on performance were discussed. The two 9.52mm OD micro-fin tubes yielded 130% and 180% greater heat transfer coefficients than the smooth tube
while the inside surface areas of the two micro-fin tubes were only 40% and 70% greater than that of the smooth tube.